or
Contact Us
BOOK A CALL
Book Call On Your Favorite Time

By Signing Up. I agree to TradeKey.com Terms of Use, Privacy Policy, IPR and receive emails related to our services

Buy - Heating Tube

  • China China  
  • Last Updated:
    Posted on: 08 Jan 2024

RFQ Details

"

Heat exchanger R410A/heating circuit water which may contain glycol for air to water heat pump

1. Fluids

Frigorific fluid: R410A. Maximum condensing temperature = 55°C. Testing pressure = 50 bars.

Heated fluid: heating circuit water (closed circuit). Maximum service pressure = 3 bars.

Cleared water should be considered in all calculations (not water containing glycol).

The water can contain 5% to 50% propylene glycol.

2. Operating conditions

Ø Condenser

Operating mode


Inlet water temperature


Outlet water temperature


Condensing temperature


Desuperheating


Subcooling

1


30°C


35°C


38°C


10°C


7°C

2


40°C


45°C


48°C


10°C


7°C

3


45°C


50°C


53°C


10°C


7°C

Ø Evaporator

Operating mode


Inlet water temperature


Outlet water temperature


Condensing temperature


Superheating

1


24°C


19°C


16°C


1°C

2


11°C


6°C


3°C


1°C

Nota: Sizing should be based on heating mode. Two alternatives should be presented: condenser only and condenser/evaporator.

Ø Heating capacity range

Models


1


2


3


4


5


6

Heating capacity, kW (application 30/35°C)


5


6.5


8


9.5


12.8


15.5

Cooling capacity, kW (application 24/19°C)


4


5.2


7.1


8


11.4


13.5

Water flow

mini/maxi, l.h-1


430/860


560/1100


690/1400


820/1600


1100/2200


1330/2700

Global annual quantity = 10 000 pieces.

3. Pressure drop

Pressure drop on water side should not exceed 25kPa in heating mode.

4. Dimension

In case of brazing plates heat exchanger, the size should not exceed:

- length: 400 mm

- width: 150 mm

- depth: depend on number of plates

In case of any other heat exchanger technology, no restriction on heat exchanger dimensions is given.

5. Condensing/evaporating temperatures measurement

The heat exchanger should be equipped with a condensing/evaporating temperature measurement device.

This device could be a tube in